Hooking up 3 Zlinx_4107 - 4/12
International Headquarters: 707 Dayton Road PO Box 1040 Ottawa, IL 61350 USA
815-433-5100 Fax 433-5104 www.bb-elec.com orders@bb-elec.com [email protected]
European Headquarters: Westlink Commercial Park Oranmore Co. Galway Ireland
+353 91 792444 Fax +353 91 792445
www.bb-europe.com orders@bb-europe.com support@bb-europe.com
PRODUCT INFORMATION B&B ELECTRONICS
18. Repeat step 1-19 for all 3 serial radio Modems
Test Serial Radio modems to make sure they are communicating
1. Hook up to the 232 port on one of the radios to a com port on a PC and power up the radio.
2. Jump 2 and 3 on the 232 ports of the 2 other radios, but only power on one of these radios.
3. Open HyperTerminal on your computer or use Range test tab on Zlinx software.
4. Set baud rate to 9600 8 even 1
5. Do a loop back to test verify connection
6. Power up the other radio and power down the other one and repeat loopback test.
Set up the 3 PLC’s (FC5A-D16RS1)
1. Use a screw driver to remove the Grey tab on the side of the PLC’s
2. Snap 485 expansion’s (FC4A-HPC3) to side of PLC’s